Wire Size Calculator
Do a wire size computation for a circuit. Enter the load, the one-way run length and the voltage, and get the smallest copper or aluminum wire gauge that handles the current and keeps voltage drop within your limit. Options for phase, continuous loads and temperature rating let you match your real installation. This is a planning estimate only; always confirm your final wire size with a licensed electrician before any real installation.
Understanding the inputs
- amps
- The current the circuit will carry, in amps. Check the appliance nameplate or the breaker rating.
- runLength
- The one-way distance from the breaker panel to the device, in feet, not the round-trip distance.
- voltage
- Most household outlets and lighting circuits run on 120V. Large appliances like dryers and ranges typically use 240V. 208V, 277V and 480V are common in commercial buildings.
- phase
- Homes use single-phase power. Choose three-phase for motors and equipment fed by a three-phase supply; it loses less voltage over the same run.
- material
- Copper carries more current than aluminum at the same gauge and has lower resistance, so aluminum wiring needs to be sized larger for the same load.
- loadType
- A continuous load runs for 3 hours or more, like lighting, an EV charger or a heater. The NEC sizes the circuit for 125% of a continuous load.
- maxDrop
- The NEC recommends keeping voltage drop to 3% on a branch circuit and 5% overall. Use 2% for sensitive electronics or when you want extra margin.
- temp
- Most home wiring and devices up to 100 amps are rated for 60°C. If every connected device is rated 75°C, you can use the higher ampacity column. When unsure, leave it at 60°C.
Wire ampacity by gauge (NEC Table 310.16)
| AWG gauge | Copper 60°C | Copper 75°C | Aluminum 60°C | Aluminum 75°C |
|---|---|---|---|---|
| 14 AWG | 15A | 20A | n/a | n/a |
| 12 AWG | 20A | 25A | 15A | 20A |
| 10 AWG | 30A | 35A | 25A | 30A |
| 8 AWG | 40A | 50A | 35A | 40A |
| 6 AWG | 55A | 65A | 40A | 50A |
| 4 AWG | 70A | 85A | 55A | 65A |
| 2 AWG | 95A | 115A | 75A | 90A |
| 1/0 AWG | 125A | 150A | 100A | 120A |
| 2/0 AWG | 145A | 175A | 115A | 135A |
| 3/0 AWG | 165A | 200A | 130A | 155A |
| 4/0 AWG | 195A | 230A | 150A | 180A |
Frequently asked questions
What wire gauge do I need for 20 amps?
12 AWG copper is the minimum for a 20 amp circuit on ampacity alone. Voltage drop can call for more: at 120V, 12 AWG stays under a 3% drop up to about 46 feet one-way, and longer runs need 10 AWG. Aluminum needs 10 AWG for 20 amps even on a short run, since aluminum carries less current at the same gauge.
Does wire run length actually matter for gauge sizing?
Yes. Long runs lose voltage, which can make lights dim and motors run hot even when the gauge is rated for the amps. This calculator works out the real voltage drop from the wire's resistance, the current and the run length, and shows it as a percent. It then picks a gauge that keeps the drop within your limit.
How do I do a wire size computation?
Start with the circuit's amps and find the smallest gauge whose ampacity covers it, using a table like the one above. Then work out voltage drop: multiply 2 (or 1.73 for three-phase) by the amps, the wire's resistance per foot and the one-way length, then divide by the voltage. If the drop is above 3%, go up a gauge and repeat. This calculator does all of those steps and shows the result. Sizing a battery bank or generator? Convert capacity with the Ah to Wh calculator and size the load with the kVA to kW calculator.
What is an acceptable voltage drop?
The NEC recommends no more than 3% on a branch circuit and no more than 5% for the feeder and branch circuit combined. These are recommendations, not hard code limits, but staying inside them keeps equipment running as designed. Pick 2%, 3% or 5% in the calculator.
Do I need a bigger wire for a continuous load?
Yes. A continuous load runs for 3 hours or more. The NEC sizes the circuit for 125% of that load, so a 16 amp continuous load is sized like a 20 amp circuit. Choose Continuous under Load type and the calculator applies the extra 25%.
Is this calculator a substitute for an electrician?
No. This tool gives a planning-stage estimate based on standard NEC ampacity tables and wire resistance. Local code amendments, conduit fill, ambient temperature, bundled cables and other factors can change the correct wire size for your specific installation. Always have electrical work verified by a licensed electrician.